IEC60092 Offshore & Marine Cables
MariTox Marine Flame Retardant Medium Voltage Cables MariTox Marine Flame Retardant Power & Control Cables MariFlex Marine Fire Resistant Power & Control Cables other

Power Distribution Cables

5000V single conductors Type E, X distribution cables

Construction

Conductor:

Stranded copper conductor tin or alloy coated where necessary for the application , conductor per ASTM or IEC

60228.

Separator tape: optional

Insulation:

Ethylene propylene rubber(EPR), or cross-linked polyethylene(XLPE) according to IEEE 1580 2010 Type E,

X,Type T, T/N, S, P, LSX and LSE as option.

Shielding: optional

Jacket: Thermosetting Polychloroprene(neoprene) according to IEEE 1580 2010 Type N, Type T, CP, CPE, L, P or

TPO jacket as option (optional for Type P with HD thicknesses).

Armor: optional and shall be nonmagnetic

Sheath: Thermosetting Polychloroprene(neoprene) according to IEEE 1580 2010 Type N, Type T, CP, CPE, L, P

or TPO sheath as option (optional except for tinned copper braid armoured cables).

Optional: For halogen-free constructions, Type LSX, LSE or LSS insulation shall be used with a Type L or TPO

jacket/sheath.

Table B.7—Typical Dimensions and weights; one conductor 5000 V; Type E and X distribution cables


AWG /kcmil
Unarmored Armored Armored and sheathed
Nom. dia. (in) Approx. weight (lb/1000 ft) Nom. dia. (in) Approx. weight (lb/1000 ft) Nom. dia. (in) Approx. weight (lb/1000 ft)
8 0.58 234 0.64 265 0.76 346
6 0.61 279 0.67 312 0.79 396
4 0.66 345 0.72 380 0.89 512
2 0.72 453 0.78 490 0.95 632
1 0.77 525 0.83 565 1 715
1/0 0.8 608 0.86 648 1.03 802
2/0 0.89 755 0.95 800 1.12 970
3/0 0.94 883 1 930 1.17 1107
4/0 1 1050 1.06 1100 1.23 1288
250 kcmil 1.04 1192 1.1 1245 1.27 1439
300 kcmil 1.1 1376 1.16 1432 1.33 1636
350 kcmil 1.15 1557 1.21 1616 1.38 1828
400 kcmil 1.2 1740 1.26 1802 1.43 2023
500 kcmil 1.3 2111 1.36 2179 1.53 2416
600 kcmil 1.38 2462 1.44 2536 1.61 2786
750 kcmil 1.49 2669 1.55 2747 1.78 3117
1000 kcmil 1.64 3835 1.7 3921 1.93 4323

NOTE—These values are for reference purposes only and should not be construed as requirements. Dimensions are based on the use of Class B conductors. Weights of armored constructions are based onaluminum braid armor. It is recommended that the user/specifier contact the manufacturer for manufacturer specific values.